Back to Products

Optrans-1P(6-10)K-4G-US — Single-Phase Grid-Tied String Inverter

A 6–10kW family of single-phase, transformerless grid-tied string inverters built for the US residential and light commercial market, with integrated rapid shutdown and AFCI fire protection.

Optrans-1P(6-10)K-4G-US is a family of single-phase, transformerless grid-tied string inverters spanning 6kW to 10kW. Each unit integrates a module-level rapid-shutdown transmitter and AFCI (arc-fault) protection to proactively reduce fire risk, and uses 3 or 4 independent MPPT trackers depending on power class. The series is certified to UL 1741SB and California Rule 21 for direct utility interconnection, and supports SunSpec-compliant monitoring with optional cellular or Wi-Fi connectivity.

Key features

  1. Max. efficiency 97.8% (97.5% CEC efficiency)
  2. String current up to 14A
  3. CA Rule 21 compliant and UL 1741SB certified
  4. SunSpec protocol with optional cellular and Wi-Fi connectivity
  5. Integrated module-level rapid-shutdown transmitter
  6. Supports module-level monitoring
  7. Optional built-in revenue-grade meter, ANSI C12.20-2010 compliant
  8. Industry-leading 3 and 4 MPPT designs
  9. AFCI protection, proactively reduces fire risk
  10. 10-year standard warranty with extension options

Models & Ordering

Power classesOptrans-1P6K-4G-US · Optrans-1P7.5K-4G-US · Optrans-1P7.6K-4G-US · Optrans-1P10K-4G-USOEM platformAlso built on the Solis-1P6-10K-4G-US inverter platform. Note: the source datasheet's cross-reference list pairs model numbers inconsistently (e.g. "Optrans-1P6K-4G-US / Solis-1P7.5K-4G-"); the four power classes in the specification table below are treated as authoritative.Ordering suffixOptrans-1P(6-10)K-4G-US-PLUS, with rapid-shutdown transmitter options: APST (APS MLRSD transmitter, required for UL3741), RSS (Tigo MLRSD transmitter), CCA (Tigo CCA).

Protection

DC reverse-polarity protectionYesGround fault monitoringYesAnti-islanding protectionYesIntegrated AFCIYesIntegrated DC switchYesMulti peak scanYesRapid shutdownBuilt-in APS or Tigo transmitterSurge protectionDC Type III / AC Type IIICompliant MLRSD productsTS4-A-F/2F/O, APsmart RSD-S/RSD-D

Connections & Communication

DC connection2 knockouts for 1" conduit at bottom, 4 knockouts for 3/4" conduit at side and back; screw-clamp terminalAC connection2 knockouts for 1" conduit at bottom, 4 knockouts for 3/4" conduit at side and back; OT terminalDisplayLCDCommunicationRS485; optional cellular or Wi-Fi

Compliance

StandardsUL1741SB, IEEE1547-2018, UL1699B, UL1998, FCC Part 15 Class B, California Rule 21, HECO Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 107.1-1

Input DC

Parameter6K7.5K7.6K10K
Max. input voltage600 V600 V600 V600 V
Rated voltage330 V330 V330 V330 V
Start-up voltage120 V120 V120 V120 V
MPPT voltage range100–500 V100–500 V100–500 V100–500 V
Max. input current14 A / 14 A / 14 A14 A / 14 A / 14 A14 A / 14 A / 14 A4 × 14 A
Max. short-circuit current22 A / 22 A / 22 A22 A / 22 A / 22 A22 A / 22 A / 22 A4 × 22 A
MPPT number / Max. input strings3 / 33 / 33 / 34 / 4

Output AC & Efficiency

Parameter6K7.5K7.6K10K
Rated output power6 kW7.5 kW7.6 kW10 kW
Max. apparent output power6 kVA7.5 kVA7.6 kVA10 kVA
Max. output power6 kW7.5 kW7.6 kW10 kW
Rated grid voltage1Φ/PE, 240V / 208V1Φ/PE, 240V / 208V1Φ/PE, 240V / 208V1Φ/PE, 240V / 208V
Rated grid frequency60 Hz60 Hz60 Hz60 Hz
Max. output current (240V grid)25 A31.3 A31.7 A41.7 A
Max. output current (208V grid)28.8 A36.1 A36.5 A43.3 A
Power factor>0.99 (0.8 leading–0.8 lagging)>0.99 (0.8 leading–0.8 lagging)>0.99 (0.8 leading–0.8 lagging)>0.99 (0.8 leading–0.8 lagging)
THDi<3%<3%<3%<3%
Max. efficiency97.8%97.8%97.8%97.8%
CEC efficiency97.5%97.5%97.5%97.5%

General Data

Parameter6K7.5K7.6K10K
Dimensions (W×H×D)13.1×28.8×9.8 in (333×732×249 mm)13.1×28.8×9.8 in (333×732×249 mm)13.1×28.8×9.8 in (333×732×249 mm)13.1×28.8×9.8 in (333×732×249 mm)
Weight45.2 lbs (20.5 kg)45.2 lbs (20.5 kg)45.2 lbs (20.5 kg)45.6 lbs (20.7 kg)
TopologyTransformerlessTransformerlessTransformerlessTransformerless
Self-consumption (night)<1 W<1 W<1 W<1 W
Relative humidity0–100%0–100%0–100%0–100%
Operating ambient temperature−13°F to 140°F (−25°C to 60°C)−13°F to 140°F (−25°C to 60°C)−13°F to 140°F (−25°C to 60°C)−13°F to 140°F (−25°C to 60°C)
Storage environment−13°F to 176°F (−25°C to 80°C)−13°F to 176°F (−25°C to 80°C)−13°F to 176°F (−25°C to 80°C)−13°F to 176°F (−25°C to 80°C)
Ingress protectionType 4XType 4XType 4XType 4X
Noise emission (typical)<30 dB(A)<30 dB(A)<30 dB(A)<30 dB(A)
Cooling conceptNatural coolingNatural coolingNatural coolingNatural cooling with internal fan
Max. operation altitude13,120 ft (4,000 m)13,120 ft (4,000 m)13,120 ft (4,000 m)13,120 ft (4,000 m)
Dimensions, topology, and environmental ratings are shared across the range except where noted.

Need a datasheet or a quote?

Send us your requirements and we’ll respond with specs and pricing.

Request a quote →